top of page

CASE STUDY 15.0
Indirect steam pump condenser
New bespoke indirect steam dump condenser designed, manufactured, and supplied by Thorne International Boiler Services Ltd. in 2020 to a UK energy from waste project as part of large turnkey integration project.

Specification
Duty
Operating pressure
Operating temperature
Design code [piping]
Year of manufacture
Industry
Scope of supply
11,000 kg/h
0.25 barg
160°C
BS EN 13480
2020
Energy from waste
Heat exchangers | Air blast coolers Expansion vessel | Piping & valves | Pumps Controls | Bypass system
- Designed to condense steam from expander / generators at 0.25 barg / 106°C to 85°C for recycling and reuse within the steam system.
System consisted of heat exchanger system, for heat transfer between steam / condensate and glycol circuit, using air blast coolers for cooling of the glycol circuit.
Automatic fan speed control for glycol temperature control on varying loads and climate conditions.
Included bypass system with associated steam pressure control system to allow for bypass and continued operation in the event of a trip.
Complete piping design, supply and installation, including valves, steels, hangers and clamps.
Supplied by Thorne International Boiler Services Ltd. turnkey to client including installation, commissioning and testing.


Thorne International Boiler Services (TIBS) offer comprehensive steam boiler services to industrial and commercial environments. From new installations and refurbishments to reverse engineering, our experienced team are committed to supporting clients from the design phase, right the way through to installation and commissioning.
bottom of page